• The W7100G maintains average discharge water temperature by staging on and off compressors, unloaders of water tower fans as required. • Provides up to six stages of cooling. • Use W7101A for expanding up to 10 cooling stages. • Advanced proportional plus integral microprocessor control algorithm minimizes droop. • Soft start to minimize compressor cycling during system start up. • Adjustable minimum on/off timing and time delay between stages of either 30 or 60 seconds. • Reset of discharge water temperature based on either outdoor air or space sensor signal. • Use C7170 Sensor for sensing water temperature. • LEDs indicate which stages of cooling are energized. • Use S963B Potentiometer for remote set point capability.MICRO PROCESSOR-BASED DISCHARGE WATEApplication Size | 0 Heat / 6 Cool |
---|
Control system | W7100 family |
---|
Contact Ratings | NC 240 VA inrush @ 40 Vac, 30 VA running @ 24 Vac |
---|
Overview | Controls discharge water temperature in reciprocating chiller and cooling tower applications. |
---|
Electrical Connections | 1/4 in. quick-connect male terminals |
---|
Compatible With | W7101 Satellite Expansion Module |
---|
Operating Temperature Range (F) | -40 F to +150 F |
---|
Operating Temperature Range (C) | -40 F to +150 F |
---|
Power Consumption | 12 VA at 24 Vac, 50/60 Hz (max). |
---|
Shipping Temperature Range (F) | -40 F to +150 F |
---|
Shipping Temperature Range (C) | -40 C to +65 C |
---|
Dimensions (in.) | 8 5/8 in. high x 6 1/2 in. wide x 3 in. deep |
---|
Dimensions (mm) | 219 mm high x 161 mm wide x 76 mm deep |
---|
Comments | 4 additional stages of cooling can be added with W7101A |
---|
Product Family
All orders are shipped same-day if the order is received by 1:00 PM Central Time. We ship worldwide.
UPS Hoilday Delivery Schedule
For more infomation about Returns visit Returns
For more informatrion about Warranty visit Warranty page.
You can also find answers to some common questions on our FAQ page
Reviews
Not reviewed yet, be the first to write one!