• An immersion type liquid-filled sensing element actuates two snap switches.
• One switch operates as a high limit control.
• The other switch operates as a low limit and/or circulator control, depending on the model.
• Controller may be mounted in any positioning and needs no leveling.
• Separate, easy-to-read, calibrated dial and setpoint adjustments for each switch.
• Differential adjustment on low limit or circulator switch.
• All adjustments accessible inside front cover.
• Push-in terminals for quick connecting.
• Single sensing element for easy installation.
• Two SPST snap switches act independently at respective temperature settings.Multiple Aquastat Controllers, High Limit and CirculatorOperating Range, Low Limit (F) | 110 F to 220 F |
---|
Overview | High limit, low limit and/or circulator controllers used to regulate boiler water temperature in gas- or oil-fired hydronic heating systems. |
---|
Operating Range, Low Limit (C) | 43 C to 104 C |
---|
Operating Range, High Limit (F) | 130 F to 240 F |
---|
Operating Range, High Limit (C) | 54 C to 116 C |
---|
Electrical Ratings | 0.25 A @ 0.25 to 12 Vdc |
---|
Electrical Rating (ignition) | Transformer Load: 360 VA |
---|
Application | High Limit and Circulator |
---|
Switching Action | SPST: High Limit & Circulator |
---|
Operating Temperature Range (F) | High Limit-- 130 F to 240 F; Low Limit-- 110 F to 220 F |
---|
Operating Temperature Range (C) | High Limit-- 54 C to 116 C; Low Limit-- 43 C to 104 C |
---|
Dimensions (in.) | 3 7/8 in. high x 4 1/8 in. wide x 2 3/4 in. deep. |
---|
Dimensions (mm) | 98 mm high x 105 mm wide x 70 mm deep. |
---|
Insulation Depth (in.) | 3 in. |
---|
Electrical Ratings (AFL) | 8A @ 120 Vac |
---|
Insulation Depth (mm) | 76 mm |
---|
Operating Humidity Range (% RH) | 0 to 95% RH, non-condensing |
---|
Electrical Ratings (ALR) | 30.6A @ 240 Vac |
---|
Differential Temperature (F) | 10 F fixed |
---|
Maximum Ambient Temperature (F) | 150 F at switches; 265 F at sensing element |
---|
Maximum Ambient Temperature (C) | 66 C at switches; 129 C at sensing element |
---|
Approvals, Underwriters Laboratories Inc | UL Listed: File No. MP466, Vol. 12, Sec. 4, Guide No. MBPR2 |
---|
Approvals, Canadian Standards Association | Certified: File No. LR95329-1 |
---|
Product Family
All orders are shipped same-day if the order is received by 1:00 PM Central Time. We ship worldwide.
UPS Hoilday Delivery Schedule
For more infomation about Returns visit Returns
For more informatrion about Warranty visit Warranty page.
You can also find answers to some common questions on our FAQ page
Reviews
Not reviewed yet, be the first to write one!
Add Review
|