• High side triac switching (B and C only).
• Freezestat protection for HVAC equipment (B and C only).
• Analog outputs (C only).
• Factory configured via EEPROM with critical user parameter default values.
• Uses LonTalk® network (E-Bus) communications protocol.
• High-speed 78 kilobit communications network.
• Conforms with Echelon® LonMark® HVAC Interoperability standard for Roof Top Unit controllers (profile number 8030).
• Free Topology Transceiver (FTT) network technology is insensitive to polarity, simplifying installation.
• Capable of stand-alone operation and has enhanced features available when using the E-Bus network communications.
• Designed for both staged heating/cooling control and modulating heating/cooling control.
• Uses either Series 60 Floating Control or PWM (W7750B only) providing modulating control for heating/cooling equipment.
• Supports two types of economizer control: modulating control and enable/disable control.
• Provides Proportional Integral Derivative (PID) temperature control.
• Uses an adaptive algorithm (patent pending) that continuously adjusts the discharge air setpoint as needed (W7750B only).
• Motion sensor interface for enhanced energy savings.
• Window sensor input for additional energy savings.Constant Volume Air Handling Unit Controller, 3 Heat / 3 Cool, 5 Digital Outputs (triacs) and 3 Analog OutputsApplication Size | 3 Heat / 3 Cool |
---|
I/O Count | 3 Analog Outputs, 6 Analog Inputs, 5 Digital Inputs, 5 Digital Outputs (triac) |
---|
Overview | The W7750A, B, C are LonMark® compliant Constant Volume Air Handling Unit Controllers used to control single zone and heat pump air handlers. |
---|
Contact Ratings | .5 A @ 24Vac (triac) |
---|
Setpoint Temperature Range (F) | 45 F to 99 F |
---|
Setpoint Temperature Range (C) | 7 C to 37 C |
---|
Used With | See Application Selection Guide (63-7046) |
---|
Application | Heat Pump Systems |
---|
Network Communications | LonWorks Bus |
---|
Commissioning Software | RapidZone |
---|
Output Type | Staged On/Off, Floating, Pulse Width Modulation |
---|
Dimensions (in.) | 5 5/8 in. high x 6 in. wide x 2 1/8 in. deep |
---|
Dimensions (mm) | 143 mm high x 152 mm wide x 54 mm deep |
---|
Operating Temperature Range (F) | -40 F to +150 F |
---|
Operating Temperature Range (C) | -40 C to +66 C |
---|
Shipping Temperature Range (F) | -40 F to +150 F |
---|
Shipping Temperature Range (C) | -40 C to +65 C |
---|
Operating Humidity Range (% RH) | 5 to 95% RH, non-condensing |
---|
Approvals, Underwriters Laboratories Inc | UL 916 (E7741) and cUL (E87741) |
---|
Approvals, Federal Communications Commission | Meets FCC part 15 Class B requirements EC Conforms to EN50081-1 (CISPR 22 Class B) and EN50082-1 |
---|
Product Family
All orders are shipped same-day if the order is received by 1:00 PM Central Time. We ship worldwide.
UPS Hoilday Delivery Schedule
For more infomation about Returns visit Returns
For more informatrion about Warranty visit Warranty page.
You can also find answers to some common questions on our FAQ page
Reviews
Not reviewed yet, be the first to write one!
Add Review
|