• Functions include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and troubleshooting.
• Subbase, amplifier and purge card are required for operation.
• Options include PC interface, keyboard display module, DATA CONTROLBUS™ MODULE, remote display module, first-out expanded annunciator, and COMBUSTION SYSTEM MANAGER™ software.
• 15 second postpurge.
• Five LEDs provide sequence information.
• Interchangeable plug-in flame amplifiers.
• Local or remote annunciation of operation and fault information.
• Nonvolatile memory retains history files and sequencing status after power loss.
• Optional remote reset capability.
• Optional report generation.
• Selectable recycle or lockout on loss of airflow or flame.
• Shutter drive output.
• Airflow switch check.
• Delayed main valve.On-Off Primary Control, 120 Vac, with Pre- and Post-Purge, Intermittent PilotOverview | Microprocessor-based integrated full-function primary burner control for automatically fired gas, oil, or combination fuel single burner applications. Provides level of safety, functional capability and features beyond conventional controls. |
---|
Approvals, Federal Communications Commission | FCC Part 15, Class B, Emissions |
---|
Application | On-Off Primary Control with Pre and Post purge |
---|
Flame Establishing Period - Pilot | 4 sec or 10 sec |
---|
Flame Establishing Period - Main | Intermittent |
---|
Approvals, Underwriters Laboratories Inc | Component Recognized, File No. MP268; Guide No. MCCZ. |
---|
PrePurge | Determined by ST7800A Purge Timer Card |
---|
Approvals, Canadian Standards Association | Certified, File No. LR95329-3. |
---|
Required Components | Q7800A,B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800A Plug-in Purge Timer Card. |
---|
Voltage | 120 Vac (+10, -15%) |
---|
Vibration | 0.5 G environment |
---|
Ambient Temperature Range (F) | -40 F to +140 F |
---|
Ambient Temperature Range (C) | -40 C to +60 C |
---|
Dimensions (in.) | 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase |
---|
Dimensions (mm) | 127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase |
---|
Approvals, Swiss RE (formerly IRI) | Acceptable |
---|
Approvals, Factory Mutual | Report No. OX4A5.AF. |
---|
Comments | Includes Pre- and Post -Purge. |
---|
Product Family
All orders are shipped same-day if the order is received by 1:00 PM Central Time. We ship worldwide.
UPS Hoilday Delivery Schedule
For more infomation about Returns visit Returns
For more informatrion about Warranty visit Warranty page.
You can also find answers to some common questions on our FAQ page
Reviews
Not reviewed yet, be the first to write one!
Add Review
|