• Operates from commercial thermostat and DCV sensor to provide a totally integrated control system.
• Mounts on M7215 Motor or ductwork.
• Used with Honeywell M7215 or Series 70 DCA.
• Combines minimum and DCV maximum damper position potentiometers with compressor staging.
• Solid state enthalpy or dry bulb changeover control.
• Terminals included for connecting optional S963B1128 Remote Potentiometer for remote minimum damper position control.
• LED indicates when free cooling is available.
• LED indicates when module is in DCV mode.
• LED indicates when exhaust fan contact is closed.
• W7213 is used with heat pump B terminal.
• W7214 is used with heat pump O terminal.Demand Control Ventilation Economizer Logic Module, 2-10 Vdc to Actuator OutputApprovals, Others | Complies with California Title 24 |
---|
Output | 2-10 Vdc to actuator |
---|
Input | Dry Bulb Temperature sensor: C7660; Mixed Air Temperature sensor: C7150; CO2 sensor: C7232 |
---|
Approvals, C-Tick | Approved |
---|
Overview | W7212, W7213, and W7214 Economizer Logic Modules are used with C7232 Demand Control Ventilation (DCV) Sensors, and solid state C7400 Enthalpy Sensors or C7660 Dry Bulb Temperature Sensors. All models proportion outdoor and return air dampers for control of free cooling in commercial HVAC equipment. |
---|
Contact Ratings | 1.5 A Run @ 30 Vac |
---|
Approvals, CE | CE Report: GV02-003 |
---|
Operating Temperature Range (F) | -40 F to +149 F |
---|
Operating Temperature Range (C) | -40 C to +65 C |
---|
Comments | Economizer Logic Module operates Series 72 actuators. |
---|
Dimensions (in.) | 4 1/8 in. high x 4 3/8 in. wide x 1 5/8 in. deep |
---|
Dimensions (mm) | 105 mm high x 111 mm wide x 41 mm deep |
---|
Operating Humidity Range (% RH) | 5 to 95% RH, non-condensing |
---|
Approvals, Underwriters Laboratories Inc | UL Listed File: E4436, Guide: XAPX, Meets UL873 plenum requirements |
---|
Product Family
All orders are shipped same-day if the order is received by 1:00 PM Central Time. We ship worldwide.
UPS Hoilday Delivery Schedule
For more infomation about Returns visit Returns
For more informatrion about Warranty visit Warranty page.
You can also find answers to some common questions on our FAQ page
Reviews