• Separate heat and cool adjustable set point levers provide adjustable deadband from 3 F to 30 F (2 C to 17 C).
• Single 2 to 22 Vdc voltage ramp provides heating/cooling signal to W7080 Load Analyzer.
• Outputs constant 12 Vdc when sensed temperature is within deadband range.
• Ramp output decreases on call for heat: increases on call for cooling.
• C7100B or C7046B Air Temperature Sensors are used to provide heating/cooling anticipation (one required for each zone thermostat) and can also be optionally used as remote return air temperature sensors with the T7080B transmitter.
• Operates on 24 Vdc supplied by W7080A Load Analyzer.
• Mounts on standard 2 x 4 in. outlet box or on nonconductive flat surface.Temperature Controller, 3 Heat / 3 CoolApplication Size | 3 Heat / 3 Cool |
---|
Control system | W7080 control system |
---|
Overview | Used in W7080 control system to provide modulating space temperature control. |
---|
Setpoint Temperature Range (C) | 13 C to 29 C |
---|
Setpoint Temperature Range (F) | 55 F to 85 F |
---|
Shipping Temperature Range (F) | -40 F to +150 F |
---|
Shipping Temperature Range (C) | -40 C to +65 C |
---|
Dimensions (in.) | 4 5/8 in. high x 2 13/16 in. wide x 1 1/4 in. deep |
---|
Approvals, Department of Defense Gudielines | Meets |
---|
Approvals, ASHRAE Guidelines | Meets ASHRAE 90-75 |
---|
Dimensions (mm) | 118 mm high x 71 mm wide x 32 mm deep |
---|
Product Family
All orders are shipped same-day if the order is received by 1:00 PM Central Time. We ship worldwide.
UPS Hoilday Delivery Schedule
For more infomation about Returns visit Returns
For more informatrion about Warranty visit Warranty page.
You can also find answers to some common questions on our FAQ page
Reviews
Not reviewed yet, be the first to write one!