• Use with AQ1000 2-wire dry contact communicating thermostats and most digital thermostats.
• 0-10 Vdc modulating output for driving a modulating/condensing boiler.
• Displays outdoor temperature on all AQ1000 Series thermostats when used with an AQ12C10 outdoor sensor (included).
• Intuitive programming interface and armchair programming (can be programmed at your desk and taken to the job site "ready-to-install").
• Customizable control settings and schedules allow for greater level of control and comfort.
• Controls up to 2 stages of heat from a single thermostat.
• Central programming of zone set points and setbacks
• Zoning Control for up to 4 zones as shipped; can be expanded to a total of 16 zones with AQ255 or AQ257 expansion zoning panels, and up to 64 zones when used with AQ254 Add-a-Temperature panels.
• Zone synchronization through Zone of Greatest Demand control.
• Domestic hot water priority and priority override protection.
• Line or low-voltage output for zoning equipment (pumps or valves).
• Boiler short cycling protection.
• Boiler post purge.
• Freeze protection.
• Pump/valve exercise.
• Boiler shock prevention from cold water returning to boiler.
• Automated test and purge feature for quick start-up and simplified troubleshooting.
• Integral 38 VA transformer with self resetting electronic fuse.
• 2 hour power supply (super-capacitor) to retain day and time settings during power outage.
• Non-volatile EPROM memory retains program settings during power outage.PROGRAMMABLE RELAY CONTROL PANEL FOR 4 ZONES OF VALVES WITH END SWITCHES.Application | Boiler control for zoned hydronic systems |
---|
Setback Program | 7 day, up to 2 setback periods/day. |
---|
Boiler Differential | 2F to 41F (1C to 23C), or Auto (minimum 2 minutes on time) |
---|
User Interface (Setting, Programming) | LCD Display and a 7 button Key Pad |
---|
Overview | The AQ25A family of AQUATROL Programmable Relay Boiler Controls provides simplified, energy-efficient control of single-temperature, residential hydronic heating systems. The AQ25A easily converts a single zone heating system into a room-by-room comfort c |
---|
Number of Zones Controlled | 4 |
---|
Boiler Heat Post Purge | Off, 10 seconds to 30 minutes (factory default is 30 seconds) |
---|
Pump/Valve exercise | 30 seconds per 2 weeks of space heating inactivity |
---|
Thermostat Compatibility | AQ1000 Series 2-wire communicating thermostats and most digital thermostats |
---|
R-C Output (on transformer) | 38 VA, 24 Vac Class II |
---|
R-C Input (on Control and Zoning Modules) | 24 Vac Class II (input on Control and Zoning Modules) |
---|
Supply/Return Sensor | Lead Length: 10 ft. (3050 mm). 10 kilohm NTC thermistor at 25 C (77 F) ±0.5F (±0.3C) up to 500 ft (150 M) using 18 AWG or larger wire |
---|
Auxiliary (Demand) Input | External dry contacts connection only |
---|
Heat Demand (Thermostat R-W) Input | External dry contacts connection only |
---|
DHW Demand Input | External dry contacts connection only |
---|
Boiler (T-T) Output Rating | 24 Vac, 0.5A, 12VA |
---|
Auxiliary Low Voltage Output Rating | 24 Vac, 0.5A, 12VA |
---|
B-B Communication Bus Terminals | Low voltage, Class II, 2-wire polarity-insensitive, digital communicating link to other Control or Zoning modules. |
---|
Zone Module Thermostat input | Low voltage, Class II, 2-wire polarity-insensitive, digital communicating with power link to AQ1000 series thermostat. |
---|
Boiler Pump Output Rating | 120 Vac/250 Vac 5A, 1/3HP |
---|
DHW Pump/Valve Output Rating | 120 Vac/250 Vac 5A, 1/3HP |
---|
Auxiliary Pump Output Rating | Dry contact output, 120 Vac/250 Vac 5A, 1/3 HP |
---|
Zone Output Contact Rating | Pumps: 120 Vac/250 Vac, 5A, 1/3 HP |
---|
Control and Zoning Panel Temperature Rating (F) | 32 F to 130 F |
---|
Control and Zoning Panel Temperature Rating (C) | 0 C to 55 C |
---|
Sensor Temperature Rating (F) | -58 F to +230 F |
---|
Sensor Temperature Rating (C) | -50 C to +110 C |
---|
Dimensions (in.) | 16 1/2 in wide x 8 in. high x 3 3/8 in deep |
---|
Operating Humidity Range (% RH) | 5 to 90% RH, non-condensing |
---|
Dimensions (mm) | 42 cm wide x 20.3 cm high x 8.5 cm deep |
---|
Type of Zoning Devices Controlled | Zone valves with end switches |
---|
Electrical Connections (Line Voltage) | Wire-clamp screw terminals, Maximum 2 x 14 AWG each on line voltage terminals |
---|
Outdoor Sensor | Lead Length: 10 ft. (3050 mm). 10 kilohm NTC thermistor at 25 C (77 F) +/- 0.5F (+/-0.3C) up to 500 ft (150 M) using 18 AWG or larger wire, beta=3892. |
---|
Replacement Parts | AQ12C10 outdoor sensor |
---|
Approvals, Canadian Standards Association | CSA C/US Certified to CSA and UL Standards, File No. LR76030 |
---|
Product Family
All orders are shipped same-day if the order is received by 1:00 PM Central Time. We ship worldwide.
UPS Hoilday Delivery Schedule
For more infomation about Returns visit Returns
For more informatrion about Warranty visit Warranty page.
You can also find answers to some common questions on our FAQ page
Reviews
Not reviewed yet, be the first to write one!
Add Review
|